F650 Firmware Revision History - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

APPENDIX G
APPENDIX G APPENDIX G. G.1MISCELLANEOUS
FIRMWARE
BOOT
CHANGES DESCRIPTION
VERSION
PROGRAM
VERSION
1.00
2.00
First version of the product (Basic Model F1G0)
Full protection scheme
1.11
2.00
New model F2G0 (inputs and outputs board type 2)
1.13
2.20
Snapshot Events included (New and All)
Oscillography up to 4 records. Maximum 70 cycles at 64 samples
per cycle, trip programmable via PLC.
Broken Conductor protection function included.
Boot program updated through F650PC program
1.14
2.20
DNP 3.0 Level 2 protocol included, over TCP/IP and UDP/IP
IRIG_B synchronization
1.20
2.25
Programmable Graphical display
Calibration included to improve measurement accuracy
1.30
2.25
Sensitive ground directional unit
Isolated Ground directional unit (in 5
Energy measurements
1.31
2.25
Enhancements in 60 Hz measurements
Extended Settings Range in Negative Sequence Overcurrent
function (46)
1.33
2.30
Forward Power function (32FP)
Demand
1.44
2.30
51PL function included (besides existing 51PH)
Control Events
Alarms
ModBus over TCP/IP
1.48
2.30
Changes in 67 units in reverse mode
ModBus TCP/IP enhancement
1.50
2.30
PROTECTION
The following operation curves have been added to F650
functionality:
IEC Long-Time Inverse
IEC Short-Time Inverse
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normally Inverse
ANSI Moderately Inverse
Rectifier Curve
User Curve A/B/C/D - Flex Curve™
Note: User Curves allow the user to program any non-standard
curve type by selecting, point by point, the Operation time.
HARDWARE
Voltage Range:Voltage Metering Range expanded from (2 to 200
Volts) to (2 to 275V)
CIO Module: For those applications requiring a high number of
inputs and outputs, F650 units can be connected to a CIO module
(Remote CAN Bus I/O module) for using up to 2 additional boards.
COMMUNICATIONS
ModBus Protocol:
ModBus User Map
Virtual Inputs (control over internal logic variables, which can be
used in the configurable logic).
DNP 3.0 Protocol
New Metering scale factors
Switchgear bits mapped to binary points
Possibility of restricting the binary points map by setting
USER INTERFACE
HMI Configurable Main Screen:
The main screen offers the possibility to select the initial logo, a
simplified Metering screen showing primary values, or both.
Snapshot Events:
Possibility of viewing snapshot events from the relay display in
models without graphical display.
GE Multilin
th
current transformer)
F650 Digital Bay Controller
G.1 MISCELLANEOUS
G.1.1 F650 FIRMWARE REVISION HISTORY
MODELS
F650BABF1G0HI
F650BABF2G0HI
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
DATE
th
June 28
2002
th
October 14
2002
December
th
20
2002
nd
January 22
2003
th
January 28
2003
st
March 31
2003
th
April 9
2003
th
May 9
2003
th
July 24
2003
September
th
5
2003
st
October 31
2003
G
G-1

Advertisement

Table of Contents
loading

Table of Contents