A.1 LOGIC OPERANDS
Digital Inputs Board F (1 to 8)
A
Supervision inputs Board F (9 to 16)
Output activation signals Board F (8 elements)
Output Reset Signals Board F (8 elements)
Contact Output Status Board F (8 elements)
Board F Status
A-2
CONT IP_F_CC1
Input 1 (CC1) Board F
CONT IP_F_CC2
Input 2 (CC2) Board F
...
...
CONT IP_F_CC8
Input 8 (CC8) Board F
CONT IP_F_CC9
Contact Input 09 (Va_COIL1) for slot F. Input voltage
(Va_COIL1)
(Va) detected, Circuit 1. Complete circuit supervised
CONT IP_F_CC10
Contact Input 10 (Vb_COIL1) for slot F. Input voltage
(Vb_COIL1)
(Vb) detected, Circuit 1. Complete circuit supervised
CONT IP_F_CC11
Contact Input 11 (Va_COIL2) for slot F. Input voltage
(Va_COIL2)
(Va) detected, Circuit 2. Complete circuit supervised
CONT IP_F_CC12
Contact Input 12 (Vb_COIL2) for slot F. Input voltage
(Vb_COIL2)
(Vb) detected, Circuit 2. Complete circuit supervised
Contact Input 13 (07_SEAL) for slot F. Current
CONT IP_F_CC13
detected. Contact output associated with current flow >
(O7_SEAL)
100 mA latched
Contact Input 14 (08_SEAL) for slot F. Current
CONT IP_F_CC14
detected. Contact output associated with current flow >
(O8_SEAL)
100 mA latched
CONT IP_F_CC15
Contact Input 15 SUP_COIL1) for slot F. Output for
(SUP_COIL1)
circuit 1 supervision element
CONT IP_F_CC16
Contact Input 16 SUP_COIL2) for slot F. Output for
(SUP_COIL2)
circuit2 supervision element
CONT OP OPER_F_01
Logic signal for Output 1 activation. Board F
CONT OP OPER_F_02
Logic signal for Output 2 activation. Board F
...
...
CONT OP OPER_F_8
Logic signal for Output 8 activation. Board F
CONT OP RESET_F_01 board F, 01 latched output reset
CONT OP RESET_F_02 board F, 02 latched output reset
...
...
CONT OP RESET_F_08 board F, 08 latched output reset
CONT OP_F_01
Contact output 1 Board F operation
CONT OP_F_02
Contact output 2 Board F operation
...
...
CONT OP_F_08
Contact output 8 Board F operation
Board F status: (0) Inactive - There is no
BOARD F STATUS
communication with the board (1) Active - There is
communication with the board
F650 Digital Bay Controller
APPENDIX A