C.1 DNP 3.0 PROTOCOL FOR F650
The following table provides a "Device Profile Document" in the standard format defined in the DNP 3.0 Subset Definitions
Document.
a) DNP V3.00 DEVICE PROFILE DOCUMENT (SHEET 2 OF 3)
(Also see the IMPLEMENTATION TABLE in the following section)
Vendor Name: General Electric Multilin
Device Name: F650 Relay
Highest DNP Level Supported:
For Requests:
For Responses: Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Inputs Changes (Object 2)
Binary Outputs (Object 10)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Maximum Data Link String Size (octets):
C
Transmitted:
Received:
Maximum Data Link Re-tries:
None
a
Fixed at 2
Configurable
Requires Data Link Layer Confirmation:
a
Never
Always
Sometimes
Configurable
C-4
Level 2
292
292
F650 Digital Bay Controller
C.1.2 DNP 3.0 DEVICE PROFILE DOCUMENT
Device Function:
Master
a Slave
Maximum Application Fragment Size (octets):
Transmitted:
Configurable up to 2048
Received:
2048
Maximum Application Layer Re-tries:
a None
Configurable
APPENDIX C