10 APPLICATION EXAMPLES

10 APPLICATION EXAMPLES 10.1EXAMPLE1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
The requirements for this setting exercise are:
Communicate the relay via serial cable or Ethernet 10/100 Base T cable using F650 PC program.
Set some Phase Time Overcurrent protection function to operate at 5A , Inverse curve IEC, Dial 0.1
Set some Output contact on board F to be operated and sealed by the operation of the phase TOC.
Set some LED to show the operation of the phase TOC
Set some Operation to reset the output contact after dropout of the phase TOC since the front F1 pushbutton.
Set some Oscillography channel to record the pickup of phase TOC and output contact closing action.
To test the operation of this Phase Time Overcurrent protection
This procedure describes the connection between any Laptop and some F650 relay using the EnerVista 650 SETUP
program
For any one of these connections check first the communication parameters as follows:
Serial Communication (RS232 front port of the relay)
With the ESC key check on the main front screen the serial communication parameters (Baud rate, parity, data bits, stop bit
and ID number).
Connect the serial cable PC-F650
Open the EnerVista 650 SETUP program in the PC and under Communication ⇓ Computer menu check that the serial
communication parameters displayed are the same read in the front of the relay. Check also that:
Control Type is set to No Control Type
Startup Mode is set toCommunicate with relay
Click ON key.
Ethernet LAN (10/100 Base T rear port of the relay)
In the Laptop choose My PC-Control Panel-Network-Protocols-Protocol TCP/IP-Advance and set in IP Address
screen the following:
IP Address 192.168.37.126
Netmask
255.255.255.0
In the front of F650 relay and pressing the ESC key display the Main Settings screen.
Move clockwise the rotating knob to choose Change Settings and press down the rotating knob.
Choose Comm Settings and press down the rotating knob.
Choose Network 0 and press down the rotating knob. It will be displayed IP Address OCT 1 and set it according to the
following table:
SEQUENCE
ACTION
----
Move rotating knob clockwise
GE Multilin
10.1 EXAMPLE1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE

10.1.2 PROCEDURE TO COMMUNICATE WITH THE RELAY

SETTING
ACTION
IP Address OCT 1
Set to 192 with rotating knob and press it down
IP Address OCT 2
Set to 168 with rotating knob and press it down
F650 Digital Bay Controller

10.1.1 DESCRIPTION OF THE EXERCISE