9 COMMISSIONING

9.15FREQUENCY ELEMENTS (81O/81U)

Set the relay to trip for the protection element being tested. Configure any of the outputs to be activated only by the
protection element being tested.
Set the relay as follows:
Apply voltage as indicated on the table, modifying frequency from the maximum threshold (48 Hz) to the minimum (46 Hz)
for 81U, and from the minimum (52 Hz) to the maximum (54 Hz) for 81O, in steps of 10 mHz.
Verify that the relay trips at the set frequency in the corresponding element with an error of 3% ó +/-50 mHz.
Apply a voltage that is lower than the "Minimum Voltage" setting, with a frequency under (81U) or over (81O) the setting,
and verify that the relay does not trip.
ELEMENTS PHASE PICKUP LEVEL
(HZ)
81U
VII
47.5
81 O
VII
52.5
GE Multilin
GENERAL SETTINGS
Nominal Frequency
50 Hz
ELEMENT SETTINGS
FREQUENCY (81)
81U
Function
ENABLED
Pickup Level
47.50 Hz
Trip Delay
2.00 sec
Reset Delay
0.00 sec
Minimum Voltage
30 V
TRIP DELAY
APPLIED
(SECONDS)
VOLTAGE (V)
2
80
25
2
80
25
F650 Digital Bay Controller
9.15 FREQUENCY ELEMENTS (81O/81U)
81O
ENABLED
52.50 Hz
2.00 sec
0.00 sec
30 V
FREQUENCY
TRIPPING TIME (S)
THRESHOLDS
THEORETICA
L
48 Hz
No trip
46 Hz
2
46 Hz
No trip
52 Hz
No trip
54 Hz
2
54 Hz
No trip
ADMISSIBLE
NA
[1.9 –2.2]
NA
NA
[1.9 –2.2]
NA
9