6.2 STATUS
Actual > Status > Switchgear Status
For a better understanding of the represented statuses in this screen, figure 6.1 shows the available "Switchgear" modules
to be programmed in the F650. Each of them has a series of inputs/outputs that are the statuses represented on this
screen. Separate signal for each switchgear device (for 1 to 16).g
Each Switchgear module can be programmed at: Setpoint > Relay Configuration >Switchgear, and its statuses are as
follows:
Table 6–24: SWITHGEAR STATUS
SWITCHGEAR 1 STATUS
SWITCH 1 A INPUT
SWITCH 1 B INPUT
SWITCH 1 A STATUS
SWITCH 1 B STATUS
SWITCH 1 OPEN
SWITCH 1 CLOSED
SWITCH 1 00_ERROR
SWITCH 1 11_ERROR
SWITCH 1 OPEN INIT
SWITCH 1 CLOSE INIT
SWGR 1 FAIL TO OPEN
SWGR 1 FAIL TO CLOSE
SWITCH X A INPUT
SWITCH X B INPUT
SWITCH X A STATUS
6
SWITCH X B STATUS
SWITCH X OPEN
SWITCH X CLOSED
SWITCH X 00_ERROR
SWITCH X 11_ERROR
SWITCH X OPEN INIT
SWITCH X CLOSE INIT
SWGR X FAIL TO OPEN
SWGR X FAIL TO CLOSE
6-16
SWITCHGEAR X STATUS
...
SWITCH X A INPUT
...
SWITCH X B INPUT
...
SWITCH X A STATUS
...
SWITCH X B STATUS
...
SWITCH X OPEN
...
SWITCH X CLOSED
...
SWITCH X 00_ERROR
...
SWITCH X 11_ERROR
...
SWITCH X OPEN INIT
...
SWITCH X CLOSE INIT
...
SWGR X FAIL TO OPEN
...
SWGR X FAIL TO CLOSE
The LED will light up when the input associated to that switchgear Contact A is activated.
The LED will light up when the input associated to that switchgear Contact B is activated.
Status associated to Switchgear contact A. It is activated once the time required for the
Switchgear module to acknowledge contact A has expired.
Status associated to Switchgear contact B. It is activated once the time required for the
Switchgear module to acknowledge contact B has expired..
Lights up when the associated switchgear is open
Lights up when the associated switchgear is closed
Output that represents the Switchgear status 00, considered as abnormal.
Output that represents the Switchgear status 11, considered as abnormal.
Programmable input that indicates the initiation of the Opening Operation for the considered
switchgear.
Programmable input that indicates the initiation of the closing Operation for the considered
switchgear.
Output that represents a failure to open, from the associated external device (opening time
exceeded)
Output that represents a failure to close from the associated external device (closing time
exceeded)
F650 Digital Bay Controller
6 ACTUAL VALUES

6.2.8 SWITCHGEAR STATUS

SWITCHGEAR 16 STATUS
...
SWITCH 16 A INPUT
...
SWITCH 16 B INPUT
...
SWITCH 16 A STATUS
...
SWITCH 16 B STATUS
...
SWITCH 16 OPEN
...
SWITCH 16 CLOSED
...
SWITCH 16 00_ERROR
...
SWITCH 16 11_ERROR
...
SWITCH 16 OPEN INIT
...
SWITCH 16 CLOSE INIT
...
SWGR 16 FAIL TO OPEN
...
SWGR 16 FAIL TO CLOSE