Omron Programmable Terminals NT631 Setup Manual page 72

Programmable terminals
Hide thumbs Also See for Programmable Terminals NT631:
Table of Contents

Advertisement

Connecting to the RS-232C Port at the Host
Setting the Front Switches
I/O port selector switch
RS-232C
RS-422A
C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1,
CPM1H CPU Units, SRM1
The connection method depends upon the model of PLC being used, as
shown in the following table.
PLC model
C200HS, CQM1
Connect to the CPU Unit's built-in RS-232C port.
C200HX/HG/HE(-Z)E
Connect to the CPU Unit's built-in RS-232C port.
Connect to one of the RS-232C ports (port A or port B) on a
Serial Communications Board.
CQM1H
Connect to the CPU Unit's built-in RS-232C port.
Connect to the peripheral port through a CS1W-CN118
Connecting Cable.
Connect to the RS-232C port (port 1) on a Serial Communi-
cations Board.
CPM1
Connect to the peripheral port through a CPM1-CIF01 RS-
232C Adapter.
CPM2A, SRM1
Connect to the CPU Unit's built-in RS-232C port.
Connect to the peripheral port through a CPM1-CIF01 RS-
232C Adapter.
CPM2C
Connect to the CPU Unit's RS-232C port or the peripheral
port through a Connecting Cable (CPM2C-CN111, CS1W-
CN118, or CS1W-CN114).
(The CPM2C-CN111 splits the Unit's Communications Port
into a RS-232C port and a peripheral port. A CPM1-CIF01
RS-232C Adapter is also required to connect to this periph-
eral port.)
Section 4-1
• I/O port selection (selector switch)
Set this to RS-232C.
• System setting (DIP SW4)
To effect the existing DIP switch
settings, set SW4 to ON.
To effect the existing PLC Setup,
set SW4 to OFF.
Note
For CPU Units manufactured before or
during June 1995 (lot No. @@65), the
existing DIP switch settings differ from
the existing PLC Setup as follows.
- DIP switch settings:
2,400 bps, 1 stop bit, even parity, 7 bit
data length
- PLC Setup:
9,600 bps, 2 stop bits, even parity, 7 bit
data length
For CPU Units manufactured from July
1995 onward (lot No. @@75), the values
specified in the DIP switch settings also
are 9,600 bps and 2 stop bits.
Connection method
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nt631c

Table of Contents