Report Type
10.10.1.6
Use the control buttons
selection by pressing the control button
cancel input, press the control button
If you confirm Report Type with the Select button, you see the following
graphic display:
Use the control buttons
to select the report type you want to use
for digital alarm transmission to the station. The panel usually tells you
what type of report to select. To select a report type, press the control
button
under the word Select. To cancel input, press the control
under the word Back.
button
The report types available are: Fast Format, Contact ID, SIA Level I, SIA
Level II, SIA Level III and Extended SIA Level III, and CID in SMS.
Note: If you select "CID in SMS" then you must store the phone number
of the ARC in Reporting, Alarms, Phone Book.
to select Report Type. Confirm your
under the word Select. To
under the word Back.
10.10.1.7. Fast Format
Use the control buttons
selection by pressing the control button
cancel input, press the control button
If you confirm Fast Format with the Select button, you see the following
graphic display:
Use the control buttons
the channels of the Fast Format report. Press the control button
under the word Select. To cancel input, press the control button
under the word Back.
If you selected Fast Format in Report Type then you can select to
allocate one of the following events to each of the 8 channels
(defaults in brackets):
Not used
Fire (default Channel 1)
PA (defaulted Channel 2)
Burglar (defaulted Channel 3)
Open/Close (default Channel 4)
Technical Alarm (default Channel 8)
RF Low Battery
Supervision Loss
RF Jamming
AC Fail
Tamper Alarm
64