MP Terminal (Pulse/PWM Output)

The MP terminal is a 10 VDC pulse output or PWM output.
The output frequency and output current can be monitored using the MP terminal on the control
circuit terminal block.
MP Selection
Select a signal to output from the following table.
If pulse output 03, 08 or 15 is selected, use the digital frequency counter. For other output
signals, use the analog meter.
Parameter
No.
C027
*1."07: LAD frequency" is the frequency reference issued by the Inverter and corresponds to Output
Frequency Monitor (d001)."00: Output frequency" is the value that is calculated reflecting vector control
compensation and stabilization control under sensorless vector control, etc.
*2.This setting is effective only when the control method is Sensorless Vector Control (A044/A244 = 03).
*3.If Frequency Conversion Coefficient (b086) is set, a gain-converted value is output for the digital output
frequency. Refer to "Output Frequency Monitor [d001]" on page 5-1.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Data
Description
*1
00
Output frequency
01
Output current
*2
02
Output torque
03
Digital output frequency
Output voltage
04
05
Input power
06
Electronic thermal load rate
*1
07
LAD frequency
Digital current monitor
08
Cooling fin temperature
10
12
Do not set.
Pulse train input monitor
15
16
Do not set.
PWM/
pulse
Full-scale value
PWM
0 to maximum frequency [Hz]
PWM
0 to 200%
PWM
0 to 200%
*3
Pulse
0 to maximum frequency [Hz]
0 to 133%
PWM
(Example: 7.5 V at 200 V for a 200 V
class)
PWM
0 to 200%
PWM
0 to 100%
PWM
0 to maximum frequency [Hz]
Refer to "MP Gain Setting" on page 5-
Pulse
43.
0 to 200°C (0°C output at 0°C or
PWM
lower)
Refer to "MP Gain Setting" on page 5-
Pulse
43.
5-4 Analog Signal
5-42