5-9 Functions Relating to Protections, Warnings and Various Output Signals

Window Comparator ( WCFV/WCFI) (Disconnection Detection FVdc/FIdc)

The Inverter activates the window comparator output when the FV/FI analog input value is
within the upper and lower limit levels of the window comparator. Analog inputs such as
disconnection detection can be monitored on a desired level.
Hysteresis widths can be set for the window comparator upper and lower limit levels.
Levels and hysteresis widths can be set separately for individual FV/FI inputs.
The analog value to be adopted upon WCFV/WCFI output can be fixed to a desired value. Set
values in FV/FI Disconnection Operation Levels (b070/b071). If "no" is set, the analog input
value will be directly reflected.
FVdc/FIdc outputs are the same as WCFV/WCFI, respectively.
Parameter
No.
b060
b063
b061
b064
b062
b065
b070
b071
C021 to C022
C026
Note: The window comparator upper/lower level settings have nothing to do with the external frequency
start/end settings.
Set the voltage limits as percentages [%] corresponding to 0 to 10 V, and current limits as
percentages [%] corresponding to 0 to 20 mA.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Function name
Window Comparator
Lower limit level + Hysteresis width ×
FV Upper Limit Level
2 (0 min.) to 100.
Window Comparator
Set an upper limit level.
FI Upper Limit Level
Window Comparator
0 to Upper limit level - Hysteresis
FV Lower Limit Level
width × 2 (100 max.)
Window Comparator
Set an upper limit level.
FI Lower Limit Level
Window Comparator
0 to (Upper limit level - Lower limit
FV Hysteresis Width
level) / 2 (10 max.)
Set a hysteresis width for the upper
Window Comparator
and lower limit levels.
FI Hysteresis Width
Analog Operation
Level at FV
0. to 100./no (ignored)
Disconnection
Set the analog value to be adopted
upon WCFV/WCFI (FVdc/FIdc)
Analog Operation
output.
Level at FI
Disconnection
27: FVdc (Analog FV disconnection
detection)
Multi-function Output
Terminal Selection
28: FIdc (Analog FI disconnection
Multi-function Relay
detection)
Output Function
54: WCFV (Window comparator FV)
Selection
55: WCFI (Window comparator FI)
Default
Data range
setting
Unit
100.
%
0.
%
5
0.
%
no
5-132