Parameter
No.
A157
C044
C052
C053
C001 to C007
C021 to C022
C026
Related functions
*1. Refer to "Frequency Operation Function" on page 5-70.
*2. Refer to "Analog Input (FV, FI)" on page 5-37.
Reference
When the PID function is used, do not set the Analog Input Filter to 500 ms (A016 = 31).
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Function name
0.0 to 25.5
PID Sleep Operation
Set the delay time until sleep operation
Delay Time
is started.
PID Deviation
0.0 to 100.0
Excessive Level
OD signal output judgment level
Feedback Comparison
0.0 to 100.0
Signal Off Level
FBV signal output judgment level
Feedback Comparison
0.0 to 100.0
Signal On Level
FBV signal output judgment level
23: PID (PID disabled)
Multi-function Input
Selection
24: PIDC (PID integral reset)
Multi-function Output
04: OD (PID excessive deviation)
Terminal Selection
31: FBV (PID FB status output)
Multi-function
Relay Output
Function Selection
5-6 Operation Functions
Default
Data
setting
0.0
3.0
100.0
0.0
A001, A005, d004