Multi-function Output Terminal Contact Selection

Whether to apply the NO or NC contact output specification can be set individually for each of
multi-function output terminals P1/EDM, P2 and multi-function relay output terminal MA, MB.
Multi-function output terminals P1/EDM, P2 are open-collector output, while multi-function
relay output terminal MA, MB are relay output.
Parameter
No.
C031
C032
C036
C031 to C032 set
values
00
(NO contact)
01
(NC contact)
Specifications of Multi-function Output Terminals P1/EDM to P2
Below are the specifications of multi-function output terminals P1/EDM and P2.
Inverter interior
Electrical characteristics
Between each terminal and PC
Voltage drop 4 V max. at power-on
Max. allowable voltage: 27 VDC
Allowable max. current: 50 mA
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Function name
Multi-function Output
00: NO (NO contact) at P1, P2, MA,
Terminal P1/EDM
NC (NC contact) at MB
Contact Selection
Multi-function Output
01: NC (NC contact) at P1, P2, MA,
Terminal P2 Contact
NO (NO contact) at MB
Selection
00: NO (NO contact) at P1, P2, MA,
Multi-function Relay
NC (NC contact) at MB
Output (MA, MB)
01: NC (NC contact) at P1, P2, MA,
Contact Selection
NO (NO contact) at MB
Power
Inverter status
supply
Normal
ON
Operating (Error)
OFF
Normal
ON
Operating (Error)
OFF
PC
P2
5-3 Input/Output Terminals
Data
Output signal status
OFF (No conduction)
ON (Conduction)
Indeterminable
ON (Conduction)
OFF (No conduction)
Indeterminable
P1
Default
Unit
setting
00
01
5-34
5