Omron SYSDRIVE MX2 SERIES User Manual page 145

Multi-function compact inverter
Hide thumbs Also See for SYSDRIVE MX2 SERIES:
Table of Contents

Advertisement

Parameter
No.
C001 to C007
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Data
Description
20
STA: 3-wire start
21
STP: 3-wire stop
22
F/R: 3-wire forward/reverse
23
PID: PID disabled
24
PIDC: PID integral reset
UP: UP/DWN function
27
accelerated
DWN: UP/DWN function
28
decelerated
29
UDC: UP/DWN function data clear
31
OPE: Forced operator
32
SF1: Multi-step speed bit 1
33
SF2: Multi-step speed bit 2
34
SF3; Multi-step speed bit 3
35
SF4: Multi-step speed bit 4
36
SF5: Multi-step speed bit 5
37
SF6: Multi-step speed bit 6
38
SF7: Multi-step speed bit 7
OLR: Overload limit switching
39
40
TL: Torque limit enabled/disabled
41
TRQ1: Torque limit switching 1
42
TRQ2: Torque limit switching 2
44
BOK: Brake confirmation
LAC: LAD cancel
46
47
PCLR: Position deviation clear
50
ADD: Frequency addition
51
F-TM: Forced terminal block
ATR: Torque reference input
52
permission
53
KHC: Integrated power clear
56
57
58
59
Reserved.
60
61
62
65
AHD: Analog command held
5-3 Input/Output Terminals
Reference item
3-wire Input Function
PID Function
Remote Operation Function
Forced Digital Operator Function
Multi-step Speed Operation
Function (Bit)
Overload Limit/Overload
Warning
Torque Limit Function
Brake Control Function
Acceleration/Deceleration
Function
Simple Position Control Function 5-157
Frequency Addition Function
Forced Terminal Block Function
Torque Control
Integrated Power Monitor
Analog Command Hold Function
Page
5-56
5-73
5-71
5-85
5-65
5
5-114
5-153
5-142
5-24
5-71
5-85
5-155
5-7
5-39
5-30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents