Omron SYSDRIVE MX2 SERIES User Manual page 191

Multi-function compact inverter
Hide thumbs Also See for SYSDRIVE MX2 SERIES:
Table of Contents

Advertisement

PID scale
When PID Scale (A075) is set, the following parameters undergo scale conversion.
(Value after conversion) = (Value before conversion) × (A075)
d004
A023
A031
Feedback Selection
Select a terminal used for the feedback signal in PID feedback selection A076.
The target value depends on the terminal selected in frequency reference A001 other than that
in A076. Also note that when A001 is set to "01: Control circuit terminal block," the setting of
FV/FI Selection (A005) is disabled.
To specify "02: Modbus communication (Modbus-RTU)" for PID Feedback Selection (A076),
transfer the data as follows.
Write the data in holding register address 0006h based on 100% representing 10,000.
Register
Number
0006h
Note: You can read and write data. However, you can read data only when Modbus-RTU is selected for
the PID feedback.
Data cannot be read under other settings.
If "03: Pulse train input" is set for PID Feedback Selection (A076), the Inverter obtains a
percent conversion result (100% at maximum frequency) of the input pulse train frequency (Hz)
as a feedback value.
For details on pulse train input frequency, refer to "Pulse Train Frequency Input" on page 5-82.
Feedforward Selection
Select a terminal used for feedforward signals in PID Feedforward Selection A079.
The A079 setting is enabled even if the terminal selected in A079 is duplicated with the terminal
selected for target value or feedback value input.
If A079 is set to "disabled", feedforward control is disabled.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
F001
A011
A012
A024
A025
A026
A032
A033
A034
Parameter
Function name
No.
PID Feedback
Selection
5-6 Operation Functions
A020
A220
A021
A027
A028
A029
A035
A101
A102
Monitor and setting
R/W
parameters
R/W
0 to 10000
A022
A030
A145
Data
Resolutio
n
5
0.01 [%]
5-76