Advertisement

5-6 Operation Functions

Frequency Addition Function

The value set in Frequency Addition Amount Setting (A145) can be added to or subtracted
from the selected frequency reference value.
To use this function, allocate "50: ADD" to any of the multi-function inputs.
A145 is added or subtracted with the ADD terminal is turned on.
Parameter
C001 to C007
Note 1: If the sign of the frequency reference is changed ((−) → (+), or (+) → (−)) as a result of operation,
Note 2: When the PID function is used, this function is also enabled for a PID target value.
5

Remote Operation Function (UP, DWN)

This function changes the Inverter output frequency using UP and DWN terminals of the multi-
function input terminal.
Allocate "27: UP" and "28: DWN" to Multi-function Input Selections (C001 to C007).
While the UP/DWN terminal is turned ON, the acceleration/deceleration time conforms to
F002, F003/F202, and F203. Switch between Controls 1 and 2 using the SET terminal which
is a multi-function input terminal to which "08: SET" is allocated.
Also note that if "01: Store frequency data" is selected for C101, the set frequency value after
UP/DWN adjustment can be stored when the power is shut off.
Parameter
C001 to C007
*1.Do not turn ON/OFF the UP/DWN terminal after shutting off the power. Otherwise, the Inverter may not
store data normally.
5-71
Function name
No.
Frequency
A145
Addition Amount
Setting
Frequency
A146
Addition
Sign Selection
Multi-function
Input Selection
the rotation direction will be reversed.
(Note that A145 is displayed in % (in increments of 0.01%).)
Function name
No.
UP/DWN Storage
C101
Selection
UP/DWN Clear
C104
Terminal Mode
Multi-function Input
Selection
Data
0.00 to 400.0 (1000.)
00: (Frequency reference ) + (A145)
01: (Frequency reference ) − (A145)
50: ADD (Frequency addition)
Data
00: Do not store frequency data
*1
01: Store frequency data
00: 0 Hz
01: EEPROM data at power-on
(value stored in the EEPROM)
27: UP (UP/DWN function
accelerated)
28: DWN (UP/DWN function
decelerated)
29: UDC (UP/DWN function data
clear)
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Default
Unit
setting
0.00
Hz
00
Default
Unit
setting
00
00