Writing Into Multiple Coils [0Fh] - Omron SYSDRIVE MX2 SERIES User Manual

Multi-function compact inverter
Hide thumbs Also See for SYSDRIVE MX2 SERIES:
Table of Contents

Advertisement

Writing Into Multiple Coils [0Fh]

Rewrites consecutive multiple coils.
Example) Change the statuses of multi-function input terminals S1 to S7/EB of the
Inverter with the slave address "1".
Change multi-function input terminals S1 to S7/EB to the statuses shown in the table below.
Function name
Coil No.
Multi-function input terminals
Terminal status
Query:
No.
1
Slave address
2
Parameter No.
3
Coil start address (MSB)
4
Coil start address (LSB)
5
Number of coils (MSB)
6
Number of coils (LSB)
7
Number of bytes
8
Change data (MSB)
9
Change data (LSB)
10
CRC-16 (MSB)
CRC-16 (LSB)
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
0007h
0008h
S1
ON
Example
Field name
(Hex)
*1
01
0F
*2
00
*2
06
00
07
02
17
00
06
98
6-5 Explanation of Each Parameter No.
Data
0009h
000Ah
S2
S3/GS1 S4/GS2
ON
ON
OFF
(Coil address) = (Coil number) − 1
17h = 0001 0111
Input terminal S7/EB
000Bh
000Ch
000Dh
S5/TH
S6
S7/EB
ON
OFF
OFF
Input terminal S1
6-14
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents