Register
Function name
No.
Communication Parity
144Eh
Selection
Communication Stop Bit
144Fh
Selection
Operation Selection on
1450h
Communication Error
Communication Error
1451h
Timeout Time
Communication Wait
1452h
Time
1453h
to
Reserved
1454h
1455h FV Adjustment
1456h FI Adjustment
1457h
to
Reserved
1458h
1459h Thermistor Adjustment
145Ah
to
Reserved
145Eh
145Fh Debug Mode Selection
1460h
to
Reserved
1463h
Communication
1464h
Selection
1465h Reserved
Co-inverter
1466h
Communication Starting
Station Number
Co-inverter
1467h
Communication Ending
Station Number
Co-inverter
1468h
Communication Starting
Selection
UP/DWN Storage
1469h
Selection
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
6-8 List of Modbus Communication (Modbus-RTU) Data
Parameter
R/W
No.
C074
R/W
C075
R/W
C076
R/W
C077
R/W
C078
R/W 0 to 1000
C081
R/W 0 to 2000
C082
R/W 0 to 2000
C085
R/W 0 to 2000
C091
R
C096
R/W
C098
R/W 1 to 8
C099
R/W 1 to 8
C100
R/W
C101
R/W
Monitor and setting
parameters
00: Disabled
01: Even
02: Odd
1: 1 bit
2: 2 bits
00: Trip
01: Trip after deceleration
stop
02: Ignore
03: Free-run stop
04: Deceleration stop
0: Timeout disabled
1 to 9999
For factory adjustment (Do
not change.)
00: Modbus communication
(Modbus-RTU)
01: Co-inverter
communication
02: Co-inverter
communication
(management)
00: 485 terminal
01: Always started
00: Do not store frequency
data
01: Store frequency data
Data
Page
resolution
0.01 [s]
1 [ms]
0.1 [%]
5-40
0.1 [%]
0.1 [%]
5-120
6
6-22
6-22
5-71
6-60