5-8 Restart Functions
Parameter
C102
C103
C001 to
C007
Example 1) Trip reset at power ON (C102 = 00, 02, 03)
RS input
AL output
(alarm signal)
Example 2) Trip reset at power OFF (C102= 01)
5
RS input
AL output
(alarm signal)
Example 3) Reset enabled when normal (C102 = 00, 01)
Output frequency
RUN command
RS input
Example 4) Reset disabled when normal (C102 = 02, 03)
Reset is disabled during operation.
Output frequency
RUN command
RS input
5-101
Function name
No.
Reset Selection
Reset Restart
Selection
Multi-function
Input Selection
Restarts according to C103.
Data
Description
Trip reset only (example 1)
Not initializing internal data such as
current values upon trip reset (Refer to
03
"Initialization Setting" on page 5-171.)
Normal: Disabled
Abnormal: Trip reset
00
0 Hz restart
01
Frequency matching restart (example 3)
02
Frequency pull-in restart (example 4)
RS: Reset
18
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Default
Unit
setting
00
00