5-1 Monitor Mode
Input Power Monitor [d014]
Displays the input power (instantaneous value) of the Inverter.
Parameter
d014
Integrated Power Monitor [d015]
Displays the integrated power (electric energy) of the Inverter.
The conversion of displayed data is performed with Integrated Power Display Scale (b079).
"d015 display" = "Actual integrated power [kWh]"/"Integrated Power Display Scale (b079)"
Example) If b079 = 100 and the displayed value is 1,000, the actual integrated power is
The integrated power value can be cleared by setting Integrated Power Clear (b078) to "01."
5
The integrated power value can also be cleared via terminal input, if "53: KHC (Integrated
power clear)" is allocated to any of the multi-function inputs.
When Integrated Power Display Scale (b079) is set to "1000", up to "999,000,000" [kWh] can
be displayed.
This parameter is saved in the EEPROM when the power is shut off.
Parameter
C001 to C007
5-7
Function name
No.
Input Power
Monitor
100,000 [kWh].
Function name
No.
Integrated Power
d015
Monitor
Integrated Power
b078
Clear
Integrated Power
b079
Display Scale
Multi-function Input
Selection
Data
0.0 to 100.0
Data
0.0 to 9999.
Displayed in increments of the setting
unit 1 kW × (b079).
1000 to 9999
Displayed in increments of the setting
unit 10 kW × (b079).
⎡100 to ⎡999
Displayed in increments of the setting
unit 1,000 kW × (b079).
00: Normal
01: Perform integrated power clear (01
is reset to 00 after the clear.)
1. to 1000.
53: KHC (Integrated power clear)
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Default
Unit
setting
−
kW
Default
Unit
setting
−
−
00
−
−
1.
−
−