Restart Upon Momentary Power Interruption/Undervoltage, Overvoltage/Overcurrent

Whether to trip or restart the Inverter upon momentary power interruption/undervoltage or
overvoltage/overcurrent can be selected.
Restart upon Momentary Power Interruption/Undervoltage, Overvoltage/Overcurrent
When a restart function is selected under Retry Selection (b001), the Inverter restarts
repeatedly for the number of times set in b005 in the case of momentary power interruption/
undervoltage, or in b010 in the case of overvoltage/overcurrent, and then trips at the next
restart. The Inverter does not trip when unlimited restart is set. Unlimited restart can be set only
for Momentary Power Interruption/Undervoltage Restart (b005).
b004 can be used to select whether the Inverter trips or not when a momentary power
interruption or undervoltage occurs while stopped.
When selecting a restart function, set the following restart conditions according to the system.
A desired function can be selected from 0 Hz restart, frequency matching restart, frequency
matching deceleration trip, and frequency pull-in restart.
Even when the Inverter is restarting, an E09 (undervoltage) trip occurs if an undervoltage
condition continues for 40 seconds.
Parameter
No.
b001
b002
b003
b004
b005
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Function name
Data
00
01
02
Retry Selection
*1*2
03
04
Allowable
Momentary Power
0.3 to 25.0
Interruption Time
Restart Standby
0.3 to 100.0
Time
00
Momentary Power
Interruption/
01
Undervoltage Trip
During Stop
*1
Selection
02
Restart During
00
Momentary Power
Interruption Count
01
Selection
5-8 Restart Functions
Description
Trip
0 Hz restart
Frequency matching restart
*3
(example 1)
Trip after frequency matching
*3 *4
deceleration stop
Frequency pull-in restart
*3
(example 1)
Restarts if the momentary power
interruption is within the set time.
(example 1)
Trips if the momentary power
interruption is beyond the set
time. (example 2)
Time until restart
Disabled (Not tripping during
stop)
Enabled (Tripping also during
stop)
Disabled while the operation is
stopped or during a deceleration
stop due to turning OFF of the
RUN command.
16 times
Unlimited
Default
Unit
setting
5
00
1.0
s
1.0
s
00
00
5-96