6-6 To Save the Change to the Holding Register (Enter Command)

6-6 To Save the Change to the Holding
Register (Enter Command)
If a holding register write command (06h) or consecutive holding register write command (10h)
is used, the new register value will become effective but it will not be stored in the Inverter's
EEPROM memory. Accordingly, once the Inverter power is cut off the status will return to the
one effective before the holding register was changed.
To store the change to the holding register in the Inverter's EEPROM memory, issue an Enter
command according to the method specified below. When the control parameters are
changed, the motor parameters must be re-calculated.In this case, also perform recalculation
with the Enter command.

Issuing Method for the Enter Command

Use a Holding Register Write command (06h) to write into the holding register for Enter
command (0900h). At this time, the value to be written into the holding register (0900h) is as
follows.
0000
0001
0002 to FFFF
6
Note. If any of the following parameters is changed, the motor parameters must be recalculated. In this
Parameter List Requiring Motor Parameter Recalculation
Parameter No.
A003/A203
A004/A204
A044/A244
A082/A282
b112
H002/H202
Note 1. The Inverter returns a response to the host when it receives an Enter command, and then executes
Note 2. Since the Inverter's EEPROM memory has a limit for the number of rewrites (approx. 100,000
6-19
Set value
case, the motor parameters can be recalculated by writing 0000h or 0002h into the Enter command
holding register.
Function name
Base Frequency
Maximum Frequency
Control Method
Motor Incoming Voltage
Selection
Free V/f Frequency 7
Motor Parameter
EEPROM memory write. You can check whether the data is being written by monitoring the data
writing signal (coil number 0049h).
times), the Inverter life may be shortened if Enter commands are frequently used.
Description
Motor parameter recalculation
Set value storage
Motor parameter recalculation and set value storage
Parameter No.
H003/H203
H004/H204
H005/H205
H020/H220 to H024/H224 Motor Parameters
H030/H230 to H034/H234 Motor Parameters
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Function name
Motor Capacity
Motor Pole Number
Speed Response
(Auto-tuning)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents