5-6 Operation Functions
Wiring Example (When STA, STP and F/R are Allocated to Multi-function Input Terminals S1 to S3/GS1)
In the case of 3-wire input, STOP (STP input) is used with NC contact. Take note that it is not
necessary to set the output selection to NC for the Multi-function Input Terminal Operation
Selection (C011 to C017) to which the STP input is allocated.

Starting Frequency

5
Set the frequency for starting Inverter output when the RUN signal is turned on.
Use mainly to adjust the starting torque.
With Starting Frequency (b082) set high, the starting current should increase. Therefore, the
current may exceed the overload limit and overcurrent protection may work to cause a trip.
Parameter
b082
RUN command
(FW input)
Output
frequency
Output voltage
5-57
S4/GS2 S3/GS1
S7/EB
S6
S5/TH
Function name
No.
Starting
Frequency
b082
STP
STA
F/R
setting
setting
setting
S2
S1
Forward/
Stop
Start
reverse
(NC contact)
(NO contact)
Data
0.10 to 9.99 (100.00)
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
SC
PSC
P24
Default
Unit
setting
0.50
Hz