Installing the UPS Internal Batteries

The UPS internal batteries are heavy (see page 130). Each battery tray holds two rows of five batteries. Use
caution when handling the heavy battery trays.
To install the battery trays into the UPS cabinet:
1.
Verify that the circuit breakers on the UPS rear panel are in the OFF (O) position
(see Figure 58 on page 71).
2.
Remove the eight screws on the battery cover plate and retain. Remove the
plate and retain. See Figure 52.
Figure 52. Removing the UPS Battery Cover Plate
3.
Slide the battery trays into the cabinet (see Figure 53). Verify that each tray is
properly aligned before sliding the tray in.
When a tray is fully installed, tuck the plastic handle on the end of the tray into
place.
4.
Reinstall the battery cover plate.