12. Confirm the selection. Press and hold the
UPS stops beeping.
Verify that the
indicator illuminates solid on each UPS, indicating that the
UPS is operating normally and any loads not connected through the load
connector are now energized.
If the
indicator on any UPS is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active alarms.
Correct the alarms and restart if necessary.
NOTE For a parallel-ready system (a single UPS installed to be part of a future parallel system), set the
Parallel Operation Settings / Parallel Operation Mode to "Capacity Mode" to prevent unnecessary alarms (see
Chapter 5, "Operation").
Each UPS should be in Normal mode. By default, Normal mode operates on the
High Efficiency setting (see "Normal Mode" on page 97).
13. To energize loads connected through the load connectors, switch all load
connector circuit breakers to the ON (
14. On any UPS, press the
15. Verify that all UPSs in the parallel system are updated to the same firmware
version.
NOTE Firmware v2.0 does not operate in a parallel system with v1.xx. All UPSs must have firmware v2.x
installed.
On each UPS, press any button on the front panel display to activate the menu
options, and then press the button until the IDENTIFICATION menu displays.
Press the
button to display the identification data, including the firmware
version.
If any firmware versions do not match, install the firmware from the supplied
BladeUPS: Documents, Firmware, and Installation Video CD or visit
www.eaton.com/powerquality to download the latest version and the
instructions for installing it.
16. If optional EBMs are installed, see "Configuring the UPS for EBMs" on page 104
to set the number of installed EBMs for each UPS.
17. To change any other factory-set defaults, see "Operation" on page 93.
NOTE Eaton recommends setting the Date and Time and the Start screen.
NOTE Verify that the Parallel Operation Settings are set appropriately for your system. For example, if you
know the load will exceed the redundancy level of the system, set the Parallel Operation Mode to "Capacity
Mode" to prevent unnecessary alarms (see Chapter 5, "Operation").
Eaton BladeUPS (12 kVA) User's Guide
STANDARD SYSTEM INSTALLATION
button for three seconds, until the
| ) position.