Advertisement

SPECIFICATIONS
Table 20. Environmental and Safety
Surge Suppression
Safety Conformance
Agency Markings
EMC (Class A)
Operating Temperature
Storage Temperature
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Heat Dissipation
Audible Noise
Leakage Current
Communication
Table 21. Battery
Configuration
Type
Monitoring
Charging (in minutes)
NOTE Charging times are approximate and are to 80% usable capacity at nominal line voltage after full load discharge.
Table 22. Standalone UPS Battery Runtimes at Full/Half Load (in Minutes)
Model
BladeUPS 12
BladeUPS 12i
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
132
Eaton BladeUPS (12 kVA) User's Guide
BladeUPS 12 Model
ANSI C62.41 Category B3
th
UL 1778 4
edition; CSA C22.2, No. 107.3
cULus, ICES, CE
FCC Part 15
Maximum wet bulb temperature with no cosmetic damage
up to 2,000 meters (6,600 ft) with 1% derating per +100 meters (330 ft)
1432 BTU/hr maximum at 100% rated load (High Efficiency mode)
4094 BTU/hr maximum at 100% rated load (Standard mode)
UPS Internal
Batteries
(40) 12V, 5 Ah
Advanced monitoring for earlier failure detection and warning
UPS Internal
kW
Batteries
12/6
4.7/13.6
12/6
4.7/13.6
S
164201649 Rev 6 www.eaton.com/powerqualtiy
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 5°C to 25°C (41°F to 77°F)
0°C to 25°C (32°F to 77°F)
-25°C to 55°C (-13°F to 131°F)
Operating: 5–95% noncondensing
Non-operating: 5–95% relative humidity, 38.7°C (101.7°F)
Up to 1,000 meters (3,300 ft) above sea level;
Up to 15,000 meters (49,000 ft) above sea level
Less than 58 dBA at 1 meter typical (Normal mode)
Less than 64 dBA at 1 meter typical (Battery mode)
<3.5 mA
DB-9: 1200–19200 baud
+1 EBM
+2 EBMs
(20) 12V, 9 Ah
(40) 12V, 9 Ah
Sealed, maintenance‐free, valve‐regulated, lead‐acid
8–10 times the discharge time
+1 EBM
+2 EBMs
9.5/27
17/42
9.5/27
17/42
BladeUPS 12i Model
EN 61000-4-6
th
UL 1778 4
edition, EN and IEC 62040-1-1
cULus, CE
EN 62040-2
+3 EBMs
(60) 12V, 9 Ah
+3 EBMs
27/60
27/60
+4 EBMs
(80) 12V, 9 Ah
+4 EBMs
34/76
34/76