Eaton Powerware BladeUPS User Manual page 97

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

8.
Wait for the UPS front panel display to illuminate.
The
indicator flashes on the UPS.
9.
Check the UPS front panel display for active alarms or notices (other than
"Batteries Disconnected"). Resolve any active alarms before continuing. See
"Troubleshooting" on page 135.
10. Switch the UPS battery circuit breaker to the ON (
11. If optional EBMs are installed, switch all EBM battery circuit breakers to the
| ) position.
ON (
12. Verify that the "Batteries Disconnected" alarm has cleared. Verify that no other
alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms
and restart if necessary.
13. Press any button on the front panel display to activate the menu options, and
then press the button until the TURN UPS ON/OFF menu displays.
14. Press the
button to display the TURN UPS ON option; press the
15. Confirm the selection. Press and hold the
UPS stops beeping.
Verify that the
indicator illuminates solid, indicating that the UPS is operating
normally and any loads not connected through the load connector are now
energized.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms
and restart if necessary.
The UPS should be in Normal mode. By default, Normal mode operates on the
High Efficiency setting (see "Normal Mode" on page 97).
16. To energize a load connected through the load connector, switch the load
connector circuit breaker to the ON (
17. Press the
button until the Start screen appears.
ESC
18. If optional EBMs are installed, see "Configuring the UPS for EBMs" on page 104
to set the number of installed EBMs.
19. To change any other factory-set defaults, see "Operation" on page 93.
NOTE Eaton recommends setting the Date and Time and the Start screen.
Eaton BladeUPS (12 kVA) User's Guide
STANDARD SYSTEM INSTALLATION
| ) position.
button for three seconds, until the
| ) position.
S
164201649 Rev 6 www.eaton.com/powerqualtiy
button.
89