Alarm or Condition
Battery test did not run.
Battery test aborted.
The UPS does not transfer to Bypass
mode.
Check Parallel Board.
Abnormal output voltage at startup.
Selective Trip.
Redundancy Loss Due to Overload.
Configuration Error and the UPS does
not start.
Possible Cause
The bypass utility was not present or was
not within limits.
Batteries were not fully charged.
User cancelled the battery test through
the front panel.
The UPS is not in the proper phase of the
cycle.
The bypass utility became unavailable
during the test.
User cancelled the battery test through
the front panel.
The bypass utility does not qualify.
Bypass mode is disabled.
The UPS is not recognizing another
paralleled UPS.
The system is not configured as parallel.
The UPS detects an internal fault.
The specified power rating of the parallel
system has been exceeded.
Parallel-Ready System only. Parallel
Operation mode is set to "Redundant
Mode."
The UPS failed to identify itself as a
paralleled UPS within two minutes after
utility power was applied.
Eaton BladeUPS (12 kVA) User's Guide
Action
Verify that the bypass utility is available and within limits.
Apply utility power for 48 hours to charge the batteries, then
restart the battery test.
Restart the battery test.
Wait for the cycle to complete (up to one month).
Verify that the bypass utility is available and within limits. Restart
the battery test. If the battery test aborts repeatedly, see "Running
Automatic Battery Tests" on page 106.
Restart the battery test.
Check the bypass utility. The UPS is receiving bypass utility power
that may be unstable or in brownout conditions.
Check that the bypass user settings are configured appropriately
(see page 96).
From the UPS Status menu, select the Units on CAN Bus option
and verify that all UPSs appear in the list.
If any UPS is missing, verify the Powerware Hot Sync CAN Bridge
Card connections and recheck the status from the UPS front
panel.
If all UPSs appear in the list, check the redundant signal wiring
(see page 76).
Set the system to internal Bypass mode.
If the condition persists, contact your service representative.
Verify the CAN wiring (see page 75).
Verify that the line cord is installed properly.
Shut down the UPS where the alarm is indicated.
Start up the UPS.
Select the Turn System On option through the front panel of the
UPS that was turned off.
If the condition persists, contact your service representative.
The load is supported, but the system lacks redundant protection
while the overload persists. Remove some of the protected
equipment.
BladeUPS parallel systems are defaulted to "Redundant Mode."
For a parallel-ready system (a single UPS installed to be part of a
future parallel system) set the Parallel Operation Settings /
Parallel Operation Mode to "Capacity Mode" to prevent
unnecessary alarms.
Verify the CAN wiring (see page 75).
If the condition persists, contact your service representative.
S
164201649 Rev 6 www.eaton.com/powerqualtiy
TROUBLESHOOTING