STANDARD SYSTEM INSTALLATION
62
Eaton BladeUPS (12 kVA) User's Guide
10. Remove the electronics module and set it aside (see Figure 47):
Remove the electronics module locking screw at the top left of the electronics
module and retain. Grasp the ring handle at the middle of the module and pull the
module slowly out of the cabinet. Pull firmly to unseat the connectors. Use two
hands to support the module.
NOTE Treat the electronics module with care to avoid damaging the fans, connectors, or internal circuitry.
Electronics Module
Locking Screw
11. If the mounting brackets are not already installed, align the two mounting
brackets with the screw holes on the sides of the UPS and secure with the
supplied 6-32 flat-head screws (see Figure 48).
12. Slide the UPS into the rack.
S
164201649 Rev 6 www.eaton.com/powerqualtiy
Figure 47. Removing the Electronics Module
Mounting Bracket
Figure 48. Installing the UPS Mounting Brackets
Ring Handle
6-32 Flat-Head