How To Replace Ups Internal Batteries - Eaton Powerware BladeUPS User Manual

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

5.
Plug the new EBM into the UPS as shown in Figure 55 on page 67.
For additional EBMs, plug the EBM cable into the battery connector on the
adjacent EBM.
6.
Remove the breaker tie from the circuit breaker on all EBMs.
7.
Switch all battery circuit breakers to the ON (

How to Replace UPS Internal Batteries

S
The UPS internal batteries are heavy (see page 130). Each battery tray holds two rows of five batteries.
Use caution when handling the heavy battery trays.
S
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when you pull
them out of the UPS.
To replace the battery trays in the UPS cabinet:
1.
Verify that the battery circuit breaker is in the OFF (O) position (see Figure 58 on
page 71).
2.
Remove the UPS front cover and set it aside (see Figure 82):
Grasp the fingergrips on both sides of the cover and pull the cover forward
firmly. Unplug the LCD cable connecting the back of the control panel to the
electronics module.
LCD Cable
Figure 82. Removing the UPS Front Cover
NOTE Disconnecting the control panel from the electronics module automatically transfers the UPS to
Bypass mode.
Eaton BladeUPS (12 kVA) User's Guide
| ) position.
C A U T I O N
S
164201649 Rev 6 www.eaton.com/powerqualtiy
UPS MAINTENANCE
121