STANDARD SYSTEM INSTALLATION
92
Eaton BladeUPS (12 kVA) User's Guide
18. If you installed an optional REPO, test the REPO function:
Activate the external REPO switch. Verify the status change on the UPS display.
Deactivate the external REPO switch and restart the UPS.
19. See "Updating the UPS Firmware" on page 128.
NOTE When adding a new UPS to a parallel system or updating one UPS's firmware, verify that all UPSs in
the parallel system are updated to the same firmware version.
NOTE The batteries charge to 80% capacity in less than 5 hours. However, Eaton recommends that the
batteries charge for 48 hours after installation or long-term storage.