Table 4. BladeUPS Bar Wiring Specifications
BladeUPS Bar
Terminal Block
Output
Input
Neutral
Safety Ground
2
* Use 13.3 mm
(6 AWG) 90_C copper wire minimum.
5.
Connect the input, output, and ground wires to the BladeUPS Bar terminal block
according to Figure 13 and Table 4. Route the three input phases and the input
neutral through the mounted or loosened ferrite assembly (see Figure 12).
Ground
Bottom Entry Terminal Block
Terminal
BladeUPS Bar
Position
Wire Function
1 [Output A]
Phase 1 Out
2 [Output B]
Phase 2 Out
3 [Output C]
Phase 3 Out
4 [Input A]
Phase 1 In
5 [Input B]
Phase 2 In
6 [Input C]
Phase 3 In
7
8
9
Ground
Eaton BladeUPS (12 kVA) User's Guide
Figure 13. BladeUPS Bar Terminal Block
Terminal Wire
Size Rating*
13.3 mm
177 mm
NOTE Wire gauge depends
on overcurrent protection
rating required (see Table 2
on page 24). Reference the
NEC, NFPA 70 for wire
Neutral
sizing.
Neutral
Neutral
2
Ground
2 mm
(14 AWG) to
52 mm
S
164201649 Rev 6 www.eaton.com/powerqualtiy
PREASSEMBLED SYSTEM INSTALLATION
Ground
Top Entry Terminal Block
Tightening
Torque
2
(6 AWG) to
2
(350 kcmil)
31.1 Nm (275 lb in)
6 Nm (50 lb in)
2
(1/O)
29