Installing The Ups Internal Batteries - Eaton Powerware Series User Manual

Bladeups 12 kva powerware series
Hide thumbs Also See for Powerware Series:
Table of Contents

Advertisement

Installing the UPS Internal Batteries

The UPS internal batteries are heavy (see page 99). Each battery tray holds two rows of five batteries. Use
caution when handling the heavy battery trays.
To install the battery trays into the UPS cabinet:
1.
Verify that the circuit breakers on the UPS rear panel are in the OFF (O) position
(see Figure 32 on page 43).
2.
Remove the eight screws on the battery cover plate and retain. Remove the
plate and retain. See Figure 26.
Figure 26. Removing the UPS Battery Cover Plate
3.
Slide the battery trays into the cabinet (see Figure 27). Verify that each tray is
properly aligned before sliding the tray in.
When a tray is fully installed, tuck the plastic handle on the end of the tray into
place.
4.
Reinstall the battery cover plate.
EATON BladeUPS
®
(12 kVA) User's Guide
C A U T I O N
Figure 27. Installing the UPS Battery Trays
S
164201649 Rev 4www.eaton.com/powerquality
INSTALLATION
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bladeups 12Bladeups 12i