Starting The Ups On Internal Bypass - Eaton Powerware BladeUPS User Manual

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

12. Confirm the selection. Press and hold the
UPS stops beeping.
Verify that the
indicator illuminates solid on each UPS, indicating that the
UPS is operating normally and any loads not connected through the Load
Connector are now energized.
If the
indicator on any UPS is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active alarms.
Correct the alarms and restart if necessary.
Each UPS should be in Normal mode. By default, Normal mode operates on the
High Efficiency setting (see "Normal Mode" on page 97).
13. To energize loads connected through the Load Connectors, switch all load
connector circuit breakers to the ON (
14. On any UPS, press the

Starting the UPS on Internal Bypass

NOTE Starting the UPS on internal bypass leaves the load unprotected.
To start a standalone UPS on internal bypass (see Figure 58 on page 71):
1.
Verify that all UPS circuit breakers are in the OFF (O) position.
NOTE The load connector breaker controls the load connector only, not the output power cord.
2.
Verify that the UPS power cord is plugged in.
3.
Verify that all UPS power cords are plugged in and secured by the plug retainers
(see Figure 63 on page 78).
4.
Switch on utility power where the UPS is connected.
5.
Switch the UPS input circuit breaker to the ON (
6.
Wait for the UPS front panel display to illuminate.
The
indicator flashes on the UPS.
7.
Check the UPS front panel display for active alarms or notices (other than
"Batteries Disconnected"). Resolve any active alarms before continuing. See
"Troubleshooting" on page 135.
8.
Switch the UPS battery circuit breaker to the ON (
9.
If optional EBMs are installed, switch all EBM battery circuit breakers to the
| ) position.
ON (
10. Verify that the "Batteries Disconnected" alarm has cleared. Verify that no other
alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms
and restart if necessary.
Eaton BladeUPS (12 kVA) User's Guide
button for three seconds, until the
| ) position.
button until the Start screen appears.
ESC
| ) position.
S
164201649 Rev 6 www.eaton.com/powerqualtiy
OPERATION
| ) position.
101