14. Connect the parallel input cord from each paralleled UPS, as shown in Figure 66:
S
Loosen the two screws on the plug retainer and slide the plug retainer out.
S
Gently loop and twist the parallel input cord as shown to minimize stress on
the cord. The loop and twist for each cord may vary depending on
configuration and strain relief to the BladeUPS Bar in the rack.
S
Insert the parallel input cord into the socket. The plug is fully seated when the
plug latches snap into place.
S
Slide the plug retainer back in and tighten the screws.
NOTE The plug retainer prevents the plug from being inadvertently unplugged.
15. Continue to "Parallel System Initial Startup" on page 90.
Figure 66. Connecting UPSs to the BladeUPS Bar (Bottom Entry Shown)
Eaton BladeUPS (12 kVA) User's Guide