COMMUNICATION
116
Eaton BladeUPS (12 kVA) User's Guide
UPS 6 REPO Terminals
2
+ Polarity
Normally-Open
1
– Polarity
2
+ Polarity
Normally-Closed
– Polarity
1
UPS 5 REPO Terminals
+ Polarity
2
Normally-Open
1
– Polarity
2
+ Polarity
Normally-Closed
– Polarity
1
UPS 4 REPO Terminals
+ Polarity
2
Normally-Open
1
– Polarity
2
+ Polarity
Normally-Closed
– Polarity
1
UPS 3 REPO Terminals
2
+ Polarity
Normally-Open
– Polarity
1
2
+ Polarity
Normally-Closed
– Polarity
1
UPS 2 REPO Terminals
2
+ Polarity
Normally-Open
1
– Polarity
2
+ Polarity
Normally-Closed
– Polarity
1
UPS 1 REPO Terminals
+ Polarity
2
Normally-Open
1
– Polarity
2
+ Polarity
Normally-Closed
– Polarity
1
Figure 81. Normally-Closed REPO Switch Wiring in a Parallel System
S
164201649 Rev 6 www.eaton.com/powerqualtiy
NOTE Remove factory-install jumper wires
and replace with REPO switch wiring.
REPO Switch
(Normally-Closed)