UPS Startup and Shutdown

To start up or shut down a UPS, see:
S
"Starting a Standalone UPS" on page 99
S
"Starting a Parallel System" on page 100
S
"Starting the UPS on Internal Bypass" on page 101
S
"Standalone UPS Shutdown" on page 102
S
"Individual Paralleled UPS Shutdown" on page 102
S
"Parallel System Shutdown" on page 103

Starting a Standalone UPS

To start a standalone UPS (see Figure 58 on page 71):
1.
Verify that all UPS circuit breakers are in the OFF (O) position.
NOTE The load connector breaker controls the load connector only, not the output power cord.
2.
Verify that the UPS power cord is plugged in.
3.
Switch on utility power where the UPS is connected.
4.
Switch the UPS input circuit breaker to the ON (
5.
Wait for the UPS front panel display to illuminate.
The
indicator flashes on the UPS.
6.
Check the UPS front panel display for active alarms or notices (other than
"Batteries Disconnected"). Resolve any active alarms before continuing. See
"Troubleshooting" on page 135.
7.
Switch the UPS battery circuit breaker to the ON (
8.
If optional EBMs are installed, switch all EBM battery circuit breakers to the
| ) position.
ON (
9.
Verify that the "Batteries Disconnected" alarm has cleared. Verify that no other
alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms
and restart if necessary.
10. Press any button on the front panel display to activate the menu options. Select
TURN UPS ON/OFF, TURN UPS ON, and press the
Eaton BladeUPS (12 kVA) User's Guide
| ) position.
| ) position.
S
164201649 Rev 6 www.eaton.com/powerqualtiy
OPERATION
button.
99