Eaton Powerware BladeUPS User Manual page 133

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

Electronics Module
Locking Screw
LCD Cable
Figure 86. Removing the UPS Front Cover and Electronics Module
4.
Label the original module with masking tape or some other identifier. Record the
serial number of the replacement module for your warranty.
If not returning the electronics module for warranty, see the following section,
"Recycling the Used Battery or UPS," for proper disposal.
5.
Insert the replacement module by sliding it carefully into the cabinet. Verify that it
seats firmly against the rear of the cabinet.
Reinstall the electronics module locking screw.
6.
Parallel configurations only. Reconnect the redundant signal cable(s).
7.
Replace the UPS front cover (see Figure 87):
Plug the LCD cable from the control panel on the front cover into the connector
on the electronics module. Use care to loop the LCD cable gently in front of the
electronics module.
Push the top of the front cover firmly into place, and then push the bottom firmly
into place.
8.
Verify that no alarms are indicated on the control panel.
9.
Transfer the UPS to Normal mode.