Trial Run Without Load (Speed Mode) - Delta ASDA-B3 Series User Manual

Hide thumbs Also See for ASDA-B3 Series:
Table of Contents

Advertisement

Test Operation and Panel Display

4.5.4 Trial run without load (Speed mode)

Before starting the trial run without load, firmly secure the motor base to avoid any danger
caused by force generated by the motor during speed changes.
4
Step 1: set P1.001 to 2 to set the control mode of the servo drive to Speed mode. Then cycle the
power to the servo drive.
Step 2: in Speed mode, set the digital input settings as shown in the following table for the trial
run.
Digital input
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
DI13
The preceding settings take the -L model for example. This table shows the settings that disable
the negative limit (DI6), positive limit (DI7), and emergency stop (DI8) functions. Thus, parameters
P2.015 - P2.017 and P2.036 - P2.040 are set to 0x000 (disabled). You can program the digital
inputs of Delta's servo drive by referring to Table 8.1 Digital input (DI) descriptions in Chapter 8.
The default setting includes the negative limit, positive limit, and emergency stop functions.
Therefore, if any alarm occurs after you complete the preceding settings, cycle the power to the
servo drive or set DI5 to On to clear the alarm. Refer to Section 4.5.2.
4-20
Parameter setting value
P2.010 = 0x0101
P2.011 = 0x0109
P2.012 = 0x0114
P2.013 = 0x0115
P2.014 = 0x0102
P2.015 = 0x000
P2.016 = 0x000
P2.017 = 0x000
P2.036 = 0x000
P2.037 = 0x000
P2.038 = 0x000
P2.039 = 0x000
P2.040 = 0x000
DI name
Function description
SON
Servo On
TRQLM
Torque limit
SPD0
Speed selection 0
SPD1
Speed selection 1
ARST
Alarm reset
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
ASDA-B3
CN1 Pin No.
DI1- = 9
DI2- = 10
DI3- = 34
DI4- = 8
DI5- = 33
-
-
-
-
-
-
-
-