Test Operation and Panel Display

4.5.4 Trial run without load (Speed mode)

Before starting the trial run without load, firmly secure the motor base to avoid any danger
caused by force generated by the motor during speed changes.
4
Step 1: set the control mode of the servo drive to Speed mode. Set P1.001 to 2 for Speed mode.
Then cycle the power to the servo drive.
Step 2: in Speed mode, the following table lists the digital input settings for the trial run.
Digital input
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
DI13
This table shows the settings that disable the negative limit (DI6), positive limit (DI7), and
emergency stop (DI8) functions. Thus, parameters P2.015 - P2.017 and P2.036 - P2.040 are set
to 0 (disabled). You can program the digital inputs of Delta's servo drive. When programming the
digital inputs for the servo drive, refer to Table 8.1 Digital input (DI) descriptions in Chapter 8.
The default setting includes the negative limit, positive limit, and emergency stop functions.
Therefore, if any alarm occurs after you complete the settings, cycle the power to the servo
drive or set DI5 to On to clear the error. Refer to Section 4.5.2.
4-20
Parameter setting value
P2.010 = 101
P2.011 = 109
P2.012 = 114
P2.013 = 115
P2.014 = 102
P2.015 = 0
P2.016 = 0
P2.017 = 0
P2.036 = 0
P2.037 = 0
P2.038 = 0
P2.039 = 0
P2.040 = 0
Symbol
Function description
SON
Servo activated
TRQLM
Torque limit
SPD0
Speed selection
SPD1
Speed selection
ARST
Alarm reset
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
-
DI disabled
ASDA-B3
CN1 Pin No.
DI1- = 9
DI2- = 10
DI3- = 34
DI4- = 8
DI5- = 33
-
-
-
-
-
-
-
-