IBM System x iDataPlex dx360 M4 7912 Service Manual page 76

Problem determination
Table of Contents

Advertisement

80010701-2701ffff • 80010901-0b01ffff
80010701-2701ffff
Numeric sensor
[NumericSensorElementName] going
high (upper non-critical) has asserted.
(Ambient Temp)
Explanation: This message is for the use case when
an implementation has detected an Upper Non-critical
sensor going high has asserted.
Internal Event: No
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0490
SNMP Trap ID: 12
Automatically notify Support: No
User response:
1.
Make sure that the fans are operating, that there
are no obstructions to the airflow (front and rear of
the server), that the air baffle is in place and
correctly installed, and that the server cover is
installed and completely closed.
2.
Check the ambient temperature. You must be
operating within the specifications (see Server
Features and specifications for more information).
3.
(Trained technician only) Replace system board.
80010701-2c01ffff
Numeric sensor
[NumericSensorElementName] going
high (upper non-critical) has asserted.
(Mezz Card Temp)
Explanation: This message is for the use case when
an implementation has detected an Upper Non-critical
sensor going high has asserted.
Internal Event: No
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0490
SNMP Trap ID: 12
Automatically notify Support: No
User response:
1.
Make sure that the fans are operating, that there
are no obstructions to the airflow (front and rear of
the server), that the air baffle is in place and
correctly installed, and that the server cover is
installed and completely closed.
2.
Check the ambient temperature. You must be
operating within the specifications (see Server
Features and specifications for more information).
58
System x iDataPlex dx360 M4 Types 7912 and 7913: Problem Determination and Service Guide
3.
Make sure that the heat sink for mezz card installed
properly.
4.
Replace mezz card.
80010701-2d01ffff
Numeric sensor
[NumericSensorElementName] going
high (upper non-critical) has asserted.
(PCH Temp)
Explanation: This message is for the use case when
an implementation has detected an Upper Non-critical
sensor going high has asserted.
Internal Event: No
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0490
SNMP Trap ID: 12
Automatically notify Support: No
User response:
1.
Make sure that the fans are operating, that there
are no obstructions to the airflow (front and rear of
the server), that the air baffle is in place and
correctly installed, and that the server cover is
installed and completely closed.
2.
Check the ambient temperature. You must be
operating within the specifications (see Server
Features and specifications for more information).
3.
Make sure that the heat sink for PCH chipset
installed well.
4.
(Trained technician only) Replace PCH chipset.
80010901-0b01ffff
Numeric sensor
[NumericSensorElementName] going
high (upper critical) has asserted.
Explanation: This message is for the use case when
an implementation has detected an Upper Critical
sensor going high has asserted.
Internal Event: No
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0494
SNMP Trap ID: 0
Automatically notify Support: No
User response: If the specified sensor is one of the
following sensors, GPU 1 Temp, K10 1 Temp, K20 1
Temp, K20X 1 Temp, Mic 1 CPU Temp, Mic 2 CPU
Temp, VGX K1 1 Temp, VGX K2 1 Temp, complete the
following steps until the problem is solved: