Customer Install Guide
Chassis
3453-C2E
Version 1.9
Note
Before using this information and the product it supports, read the information in
"Safety notices" on page 5, "Notices" on page 37, the IBM Systems Safety Notices
manual, G229-9054, and the IBM Environmental Notices and User Guide.
© Copyright IBM Corporation 2019, 2020, 2021.
Customer Install Guide, 2U Chassis
1

Advertisement

Table of Contents
loading

Summary of Contents for IBM 3453-C2E

  • Page 1 Note Before using this information and the product it supports, read the information in “Safety notices” on page 5, “Notices” on page 37, the IBM Systems Safety Notices manual, G229-9054, and the IBM Environmental Notices and User Guide. © Copyright IBM Corporation 2019, 2020, 2021.
  • Page 2 This edition applies to IBM Cloud Pak for Data System Components. Revised November 2021 © Copyright IBM Corporation 2019, 2020, 2021. US Government Users Restricted Rights – Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.
  • Page 3: Table Of Contents

    Cloud Pak for Data System 2U chassis description ............15 Cloud Pak for Data System 2U chassis hardware specifications ........16 3453-C2E, Cloud Pak for Data System (2U server chassis) ........16 Operating Environment ....................17 Rack Requirements ....................... 18 Rack Space ........................
  • Page 4: Safety

    Ennen kuin asennat tämän tuotteen, lue turvaohjeet kohdasta Safety Information. Avant d'installer ce produit, lisez les consignes de sécurité. Vor der Installation dieses Produkts die Sicherheitshinweise lesen. Prima di installare questo prodotto, leggere le Informazioni sulla Sicurezza. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 5: Safety Notices

    Read any additional safety information that comes with your system or optional device before you install the device. D005 DANGER: When working on or around the system, observe the following precautions: © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 6 Electrical voltage and current from power, telephone, and communication cables are hazardous. To avoid a shock hazard: If IBM supplied the power cord(s), connect power to this unit only with the IBM provided power cord. Do not use the IBM provided power cord for any other product.
  • Page 7 (D005) C002 CAUTION: Only trained service personnel may replace this battery. The battery contains lithium. To avoid possible explosion, do not burn or charge the battery. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 8 (C026) IBM® servers can use I/O cards or features that are fiber-optic based and that utilize lasers or LEDs. Laser compliance IBM servers may be installed inside or outside of an IT equipment rack.
  • Page 9 NEC, IEC 60950 and IEC 62368, The Standard for Safety of Information Technology Equipment. (R001 part 1) DANGER: Observe the following precautions when working on or around your IT rack system: © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 10 It is the responsibility of the customer to ensure that the outlet is correctly wired and grounded to prevent an electrical shock. (R001 part 1) R007 © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 11 DANGER: Hazardous voltage, current, or energy levels are present inside any component that has this label attached. Do not open any cover or barrier that contains this label. (L001) L002 © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 12 In addition, do not lean on rack-mounted devices and do not use them to stabilize your body position (for example, when working from a ladder). (L002) C010 (L003) © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 13 (English translation: After providing the main product, if additional power cord is required, the cord is handled for repair/maintenance/mending purpose.) © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 14: Publications

    Publications The following IBM documentation is available on the Safety and Regulatory CD included with your Cloud Pak for Data System rack & components: **** General Information Guides **** • Rack Safety Information • IBM Enterprise Slim Rack Safety Instructions •...
  • Page 15: Cloud Pak For Data System 2U Chassis Description

    The chassis is can be installed in an IBM Cloud Pak rack or a customer supplied rack meeting the guidelines in the Customer Install Guide, Rack and System document included on the Safety and Regulatory CD shipped with your Cloud Pak for Data System components.
  • Page 16: Cloud Pak For Data System 2U Chassis Hardware Specifications

    2U chassis, including dimensions, electrical power and cooling. . All component installation documents are available on the Safety and Regulatory CD that comes with your Cloud Pak for Data System components. 3453-C2E, Cloud Pak for Data System (2U server chassis) [see Notes 1, 2] Table 1...
  • Page 17: Operating Environment

    [4] Unit must acclimate to data center environment before unboxing to prevent condensation. [5] PDUs do not have fresh air cooling and can function in 60C (140F) environments © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 18: Rack Requirements

    Ensure that the rack in which you plan to install the system meets the space requirements outlined in the following figure: Figure 1: Top down view of installed chassis with 4-point horizontal mounting © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 19: Location In The Rack

    Location in the Rack The base IBM Cloud Pak for Data System consists of four main components (1G switch, 25G switch, two compute chassis) that are designed to be integrated in the same rack with PDUs. The recommended component placement is shown in Figure 2 below.
  • Page 20 • Expansion chassis are marked “EXPANSION”. • The base system 25G switch is marked #3 and the base system 1G switch is marked #4. Expansion switches are marked “EXPANSION”. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 21 Labeled “1” Chassis 1 1U Blank Panel The Cloud Pak for Data System requires all IBM supplied and serviceable components to be installed below the 42U height. Components on slides, such as server chassis and connector nodes, must be located at or below U26.
  • Page 22: Package Contents

    The transceiver kit includes the following parts: – Sixteen transceivers Note: KEEP ALL POWER CORDS, SIGNAL CABLES AND TRANSCEIVERS WITH THE INSTALLED CHASSIS FOR USE BY IBM INSTALLERS. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 23: Chassis Installation Procedure

    Read the Rack safety notices, Pub # G229-9054 included with the unit. C010 - This unit weighs approximately 121.2lb (55kg). IBM recommends the use of an appropriate lifting device to position the chassis on the rails. Rack rail parts inventory The enclosure comes with all of the hardware that is necessary for you to install the enclosure in the rack cabinet.
  • Page 24: Install Slide Rails Into The Rack

    4. Push the slide rail so that the pins and the latch go into the place. Note: The holes on the rack will either be square-shaped or round-shaped. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 25 6. Repeat steps 2 to 5 to install the other slide rail. Make sure that each slide rail is securely engaged in the flange by inspecting that the hook has caught and by sliding back and forward to ensure the slide does not pop out. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 26: Install The Enclosure On The Slide Rails

    Install the enclosure on the slide rails C010 - This unit weighs approximately 121.2lb (55kg). IBM recommends the use of an appropriate lifting device to position the chassis on the rails. Server nodes are preconfigured for their specific slots (1, 2, 3 & 4) in the chassis and they must not be removed from the chassis during the chassis installation process.
  • Page 27: Slide The Enclosure Into The Rack

    C010 - This unit weighs approximately 121.2lb (55kg). IBM recommends the use of an appropriate lifting device to position the chassis on the rails. Figure 9. Enclosure 5. Tilt and lower the enclosure; then, push the slides toward the enclosure and make sure the farthest nailheads go into the slots on the slides.
  • Page 28: Install The Cable Management Arm

    For these reasons and more, the cable management arms are required. Should you choose not to install the management arms, IBM will not be able to install or support your Cloud Pak for Data System. Should they be removed after installation, you will void your system warranty and onsite service will not be provided.
  • Page 29 3. After verifying the cable management arm is on the left side or reversing the cable management arm, align the inner mounting clip with the inner tab on the slide, then push it until it snaps into place. Figure 15. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 30 DO NOT BLOCK ANY INLET OR EXHAUST DUCTS, VENTS OR PORTS KEEP ALL POWER CORDS, SIGNAL CABLES AND TRANSCEIVERS WITH THE INSTALLED CHASSIS FOR USE BY IBM INSTALLERS. DO NOT POWER-ON THIS CHASSIS. POWER ON WILL BE DONE BY YOUR IBM INSTALLATION TEAM.
  • Page 31: Electronic Emissions Notices

    Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. Proper cables and connectors are available from IBM-authorized dealers. IBM is not responsible for any radio or television interference caused by using other than recommended cables and connectors or by unauthorized changes or modifications to this equipment.
  • Page 32 EU-Mitgliedsstaatenund hält die Grenzwerte der EN 55032 Klasse A ein. Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu installieren und zu betreiben. Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden. IBM übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen, wenn das Produkt ohne Zustimmung von IBM verändert bzw.
  • Page 33 Erweiterungskomponenten von Fremdherstellern ohne Empfehlung von IBM gesteckt/eingebaut werden. EN 55032 Klasse A Geräte müssen mit folgendem Warnhinweis versehen werden: "Warnung: Dieses ist eine Einrichtung der Klasse A. Diese Einrichtung kann im Wohnbereich Funk-Störungen verursachen; in diesem Fall kann vom Betreiber verlangt werden, angemessene Maßnahmen zu ergreifen und dafür aufzukommen."...
  • Page 34 이 기기는 업무용 환경에서 사용할 목적으로 적합성평가를 받은 기기로서 가정용 환경에서 사용하는 경우 전파간섭의 우려가 있습니다. People's Republic of China Notice 警 告 此为 A 级产品,在生活环 境中,该产品可能会造成无 线电干扰。在这种情况下, 可能需要用户对其干扰采取 切实可行的措施。 © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 35 This product may cause interference if used in residential areas. Such use must be avoided unless the user takes special measures to reduce electromagnetic emissions to prevent interference to the reception of radio and television broadcasts. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 36: Regulatory And Compliance

    Regulatory and Compliance © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 37: Notices

    Consult your local IBM representative for information on the products and services currently available in your area. Any reference to an IBM product, program, or service is not intended to state or imply that only that IBM product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any IBM intellectual property right may be used instead.
  • Page 38 Web sites. The materials at those Web sites are not part of the materials for this IBM product and use of those Web sites is at your own risk. IBM may use or distribute any of the information you supply in any way it believes appropriate without incurring any obligation to you.
  • Page 39 All of these names are fictitious and any similarity to the names and addresses used by an actual business enterprise is entirely coincidental. © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 40: Copyright License

    You may copy, modify, and distribute these sample programs in any form without payment to IBM, for the purposes of developing, using, marketing or distributing application programs conforming to the application programming interface for the operating platform for which the sample programs are written.
  • Page 41: Trademarks

    IBM, the IBM logo, ibm.com® and Netezza® are trademarks or registered trademarks of International Business Machines Corporation in the United States, other countries, or both. If these and other IBM trademarked terms are marked on their first occurrence in this information with a trademark symbol (® or ™), these symbols indicate U.S.
  • Page 42: Readers' Comments

    IBM business partner, or your authorized remarketer. When you send comments to IBM, you grant IBM a nonexclusive right to use or distribute your comments in any way it believes appropriate without incurring any obligation to you. IBM or any other organizations will only use the personal information that you supply to contact you about the issues that you state on this form.
  • Page 43 © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...
  • Page 44 Part Number: 03GJ005 Printed in Mexico © Copyright IBM Corporation 2019, 2020, 2021. Customer Install Guide, 2U Chassis...