Discrete Inputs (R41,070); Relay Outputs (R41,080); Ma Input (R41,090) [Mr 200]; Ma Output (R41,110-41,111) - Siemens MAG 1100 Operating Instructions Manual

Electromagnetic flowmeters
Table of Contents

Advertisement

Discrete Inputs (R41,070)

This table shows the current status of the discrete inputs. Only register 41,070 is used.
Discrete Input
1
2

Relay Outputs (R41,080)

This table shows the current status of the relays. A reading of 0 means that the relay
function is not asserted and a 1 means that it is asserted. For example, a 1 for a pump
relay means that the pump is running.
Relay
1
2
3
4
5
6
Values are written to control a relay only if the Relay Control Function (P111) is set to
communications (65). See

mA Input (R41,090) [MR 200]

The mA input is scaled from 0 to 2,000 (0 to 20 mA multiplied by 100). P254 displays the
value of the input. This parameter is indexed by the input number.

mA Output (R41,110-41,111)

The mA output is scaled from 0 to 2,000 (0 to 20 mA multiplied by 100). This is displayed in
P911.
Pump Control (R41,400 – R41,474)
Only relays set for pump control (P111 = 50 to 52) are available. These registers have no
effect on relays programmed for other uses.
Pump ON Setpoint (R41,420 – R41,425)
The ON setpoint level (P112) for the referenced pump relay.
The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is
shown in the register as 5402.
Page 100
MultiRanger 100/200 – INSTRUCTION MANUAL
Data Address
41,070, bit 1
41,070, bit 2
Data Address
41,080, bit 1
41,080, bit 2
41,080, bit 3
41,080, bit 4
41,080, bit 5
41,080, bit 6
Relay Function Codes (P111 Only)
on page 110.
7ML19981FB05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag 1100 fMag 3100Mag 3100 pMag 5100 wMag 5000Mag 6000

Table of Contents