Set Relays to ALTERNATE DUTY ASSIST
Parameter
P111
P111
P111
Set the ON Setpoints
Parameter
P112
P112
P112
Set the OFF Setpoints
Parameter
P113
Setting a Pump Up (Reservoir) Group
Sets a group of three pumps to pump up a reservoir.
Page 58
MultiRanger 100/200 – INSTRUCTION MANUAL
Index
Value Description
1
52
2
52
3
52
Index
Value Description
1
1.0m
2
1.1m
3
1.2m
Index
Value Description
0
0.5m
MultiRanger
P007
Inflow
Sets the pump relays (index 1, 2, and 3) to
ALTERNATE DUTY ASSIST.
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
P006
Outflow
7ML19981FB05