Measurement Verification (P710 To P713) - Siemens MAG 1100 Operating Instructions Manual

Electromagnetic flowmeters
Table of Contents

Advertisement

P708 Volume Rate Display [MR 200]
The rate of change of volume in percent of maximum volume per minute.
Please note that this feature applies to the MultiRanger 200 only.
Primary Index
Values
Related
This value is used internally to calculate inflow in pumped volume applications (P622=3).
Press READING

Measurement Verification (P710 to P713)

P710 Fuzz Filter
Use this to stabilize the reported level, due to level fluctuations (such as a rippling or
splashing liquid surface) within the Echo Lock Window (P713).
Primary Index
Values
Altered by
Related
This value (in % of Span, P007) is automatically altered when Maximum Process Speed
(P003) is altered. The higher the value entered, the greater the fluctuation stabilized.
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Single Point Model
Global
Range: -999 to 9999 (view only)
P622 Inflow / Discharge Adjust
to toggle between percent and volume.
Single Point Model
Global
Range: 0 to 100 (0 = off)
P003 Maximum Process Speed
P007 Span
P713 Echo Lock Window
Dual Point Model
Transducer
Dual Point Model
Transducer
Page 187