Checking Volume Characterization [Mr 200]; Checking Ocm Flow Characterization [Mr 200] - Siemens MAG 1100 Operating Instructions Manual

Electromagnetic flowmeters
Table of Contents

Advertisement

The effect of the ARROW key is determined by the state (rate of rise or fall) immediately
before the key is pressed.
Action
State (prior to pressing key)
Stop
Rise at 1% of Span / second
Rise at 4% of Span / second (max.)
Press
Fall at 1% of Span / second
Fall at 4% of Span / second
Stop
Rise at 1% of Span / second
Press
Rise at 4% of Span / second (max.)
Fall at 1% of Span / second
Fall at 4% of Span / second (max.)
When the level rises to 100% or falls to 0%, it reverses direction at the same rate.

Checking Volume Characterization [MR 200]

To confirm universal volume calculations (P050 = 9, 10) are correct:
1.
Go to P920.
2.
Key in a level associated with a known volume.
3.
Press ENTER
4.
Check the returned volume against the manufacturer's chart.
5.
Change parameters P054 and P055, as required.
6.
Repeat steps 2 to 5 until the volume curve is verified.

Checking OCM Flow Characterization [MR 200]

To confirm universal flow calculations (P600 = 4, 5) are accurate:
1.
Go to P925.
2.
Enter a level with a known flow.
3.
Press ENTER
4.
Check the returned flow against the manufacturer's chart.
5.
Change parameters P610 and P611, as required.
6.
Repeat steps 2 to 5 until the flow curve is verified.
Page 86
MultiRanger 100/200 – INSTRUCTION MANUAL
.
.
Effect
Rise at 1% of Span / second
Rise at 4% of Span / second (max.)
No effect
Stop
Fall at 1% of Span / second
Fall at 1% of Span / second
Stop
Rise at 1% of Span / second
Fall at 4% of Span / second (max.)
No effect
7ML19981FB05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag 1100 fMag 3100Mag 3100 pMag 5100 wMag 5000Mag 6000

Table of Contents