Terminal Board

The terminal board on the MultiRanger allows all inputs and outputs to be connected
simultaneously.
Recommended torque on terminal clamping screws.
Note:
• 0.56 - 0.79 Nm
• 5 - 7 in.lbs
Please do not overtighten the screws.
TB2
2
1
RELAY 1
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6

Cables

The MultiRanger transceiver requires a shielded two-wire connection to the transducer.
Connection
mA input and mA output
sync, Temperature sensor,
discrete input, dc input
Transducer
Relay output
AC input
1.
Preferred shielding is braided screen.
Page 16
MultiRanger 100/200 – INSTRUCTION MANUAL
TB1
12-30 V
DC Version
2 copper conductors, twisted, with shield
2
300V 0.5-0.75 mm
(22 - 18 AWG)
Maximum length: 365 m
Do not use a coaxial transducer cable extension with the
MultiRanger. Electrical noise interference affects
performance.
Relay to be copper conductors per local requirements to
meet 250 V 5A contact rating.
TB1
L2/N L1
SYNC
mA INPUT
SHIELD
1
4 - 20 mA
OUTPUTS
2
TS-3
SHIELD
1
2
DISCRETE
INPUTS
COM
RS485
A
B
Cable Type
1
/drain wire,
TB3
7ML19981FB05