Pumped Volume Totalizer (P622) [MR 200]

The Pumped Volume Totalizer is a MultiRanger 200 feature only.
If the eight-digit totalizer display or a remote totalizer contact closure are desired, alter
the following parameters.
P622 Inflow / Discharge Adjust [MR 200]
The method used to calculate the volume pumped, for pumped total Operation (P001 = 7).
Primary Index
Values
Related
* or discharge
Page 174
MultiRanger 100/200 – INSTRUCTION MANUAL
Single Point Model
Global
1 = inflow * / pump cycle
When the pump is off, the MultiRanger estimates the volume of inflow
by recording the rate at which the liquid level changes. When the
pump is operating, the estimated inflow volume is added to the
pumped volume total. When the pump stops, the pumped volume of
the previous pump cycle is added to the total volume pumped in the
totalizer.
2 = inflow * ignored
Inflow is assumed to be 0 while pumps are running.
3 = inflow * / rate (preset)
Volume pumped is adjusted for inflow. Inflow rate is estimated by
assuming that the rate calculated (P708) just prior to the start of the
pump cycle remained constant during the pump cycle. Inflow rate is
averaged using rate filter (P704), rate update time (P705) and rate
update distance (P706) to control how the average rate is calculated.
P001 Operation
P704 Rate Filter
P705 Rate Update Time
P706 Rate Update Distance
P708 Volume Rate Display
Dual Point Model
Transducer
7ML19981FB05