Backup Level Override - Siemens MAG 1100 Operating Instructions Manual

Electromagnetic flowmeters
Table of Contents

Advertisement

P062 Offset Reading
Adds the specified value to the level reading, usually to reference the reading to sea level
or another datum level.
Primary Index
Values
Related
The operation of the device is not affected by the Offset Reading. This value is used for
display purposes only. All control measurements are still referenced to Empty.

Backup Level Override

Use this feature to override the ultrasonic reading by a discrete input such as a
contacting point device. The ultrasonic reading will be fixed at the programmed switch
level until the discrete input is released.
The ultrasonic device makes decisions based on the override values.
P064 Reading Override Enable
Sets the discrete input to act as the source for a level reading override.
Primary Index
Values
Related
P065 Reading Override Value
This value is substituted for the current reading when the selected discrete input is
enabled and activated.
Primary Index
Values
Alters
Related
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Level
Range: -999 to 9999
Preset: 0.000
P920 Reading Measurement
Transducer
0
*
OFF: No override.
1-2
ON: Number = discrete input of override signal
P065 Reading Override Value
P270 Discrete Input Function
Transducer
Range: 0.0 to 9999
Current reading
P001 Operation
P005 Units
P006 Empty
P007 Span
P064 Override Enable
Page 129