Set Relays to FIXED DUTY BACKUP [MR 200]

Parameter
P111
P111
P111
Set the Relay ON Setpoints [MR 200]
Parameter
P112
P112
P112
Set the Relay OFF Setpoints [MR 200]
Parameter
P113

Set Relays to ALTERNATE DUTY SERVICE [MR 200]

Parameter
P111
P111
P111
P122
P122
P122
Set the Relay ON Setpoints [MR 200]
Parameter
P112
P112
P112
Set the Relay OFF Setpoints [MR 200]
Parameter
P113
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
Index
Value Description
1
51
Sets the pump relays (index 1, 2, and 3) to
FIXED DUTY BACKUP . Only one pump will
2
51
ever run at one time.
3
51
Index
Value Description
1
0.4m
Sets the three setpoints for the pump relays.
The setpoints remain attached to the pump
2
0.3m
relays.
3
0.2m
Index
Value Description
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
Index
Value Description
1
54
Sets the pump relays (index 1, 2, and 3) to
2
54
SERVICE RATIO DUTY ASSIST
3
54
1
25
Sets the ratio to: 25% – Pump One
2
50
3
25
Index
Value Description
1
0.4m
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
2
0.3m
Subsequent cycles rotate the setpoints
3
0.2m
among the pumps.
Index
Value Description
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
50% – Pump Two
25% – Pump Three
Page 61