Example [MR 200 only]
P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpoint) for universal
volume calculation. The illustration indicates how you can set secondary indexes to
specific functions.
[6 = 2m]
[3 = 1.5m]
[1 = 0.75m]
P054 [1, 1 ] = .75m
P054 [2, 1 ] = 8m

Starting Measurement

The MultiRanger startup varies between single and dual point models.

Single Point Models

The MultiRanger starts in DISTANCE mode with the transducer preset for the XPS-10 and
an empty distance of 5 meters. Change the following parameters to reflect your
application parameters.
Parameter
P001
P002
P003
P004
P005
P006
P007
7ML19981FB05
MultiRanger 100/200 – INSTRUCTION MANUAL
A
P054 [1,6] = 2m
P054 [1,3] = 1.5m P054 [1,1] = .75m
P054 [2,6] = 8m
P054 [2,3] = 5.5m P054 [2,1] = 2.75m
1
A
B
C
sets breakpoint 1 on transducer 1 to .75m.
sets breakpoint 1 on transducer 2 to 2.75m.
Index
Value Description
G
1
G
1
G
2
G
104
G
1
G
12
G
10
B
P054
2
A
B
C
Operation = level
Material = liquid
Maximum Process Speed = medium
Transducer = XPS-15
Units = meters
Empty = 12m
Span = 10m
C
[6 = 8m]
[3 = 5.5m]
[1 = 2.75m]
Page 37